Intelligent Building Series C-Bus Infrared Transmitter Installation Instructions
Note:
Care must be taken when using the 5100HSC High Speed Serial Cable. Please
note the following recommendations:
• The 5100HSC High Speed Serial Cable contains custom electronics (I
2
C),
and is approximately 1 metre in length. Do not attempt to extend the length of
this pre-terminated cable. If additional distance is required then use an
RS232 extension lead (maximum recommended length 20m).
• The custom electronics imbedded within the 5100HSC are powered from the
5V rail provided by the PC serial port.
• When the 5100HSC is connected to the 5034NIRT Infrared Transmitter Unit
the C-Bus Network is effectively grounded. This is generally not
recommended, and can seriously affect the operation of the C-Bus Network.
Do not leave the 5100HSC permanently connected
.
• Special PC Communications Port Settings are not necessary (eg start bits,
stop bits, baud, parity etc) as the CIRCA software will override these settings
as required.
4.0 Status Indicators
4.1 Unit IR1 Indicator:
If the Unit is powered and functional, the UNIT IR1 indicator will be illuminated
and steady. This indicator may also flash to indicate C-Bus Network
Communications traffic is being seen by the Unit.
Indicator Status Meaning
On Power on and functional
Flashing C-Bus communications in progress
Off Unit has no power
Super-Bright Flashing* IR Transmission in progress – Channel One
4.2 C-Bus IR2 Indicator:
This indicator shows the status of the C-Bus Network at this Unit. If sufficient
network voltage and a valid C-Bus clock signal are present then the “OK” signal
will be displayed (steady on). If a network is connected which has more current
load than the power supplies can support, this indicator will flash to show a
marginal network voltage. If there is no C-Bus Network Clock present then this
indicator will not light.
Indicator Status Meaning
On C-Bus Network operational
Flashing Insufficient power to support network
Off No C-Bus Clock present or insufficient power to
support network or C-Bus not connected (check
terminations)
Super-Bright Flashing* IR Transmission in progress – Channel Two
* Note that this feature can be disabled using the CIRCA software.
© Copyright 2002 Clipsal Integrated Systems Pty Ltd Page 7