Intelligent Building Series C-Bus Infrared Transmitter Installation Instructions
3.0 Installation Instructions
A typical installation of the 5034NIRT C-Bus Infrared Transmitter is shown below:
3.1 Mounting Considerations
• The E5034NIRT Unit is a British Standard Wall Plate, and may only be mounted
using deep style wall boxes (Clipsal Catalogue Number E157). Do not use the
shallow wall box (E157S).
• All other units may be mounted using any of the standard Clipsal Australian
Pattern Wall Boxes and other Mounting Accessories.
• It is recommended that the Unit be mounted close to the floor, and discreetly
located behind the control equipment. This will ensure a tidy installation.
3.2 Infrared Emitter Leads
• The two IR output channels are connected by means of two 3.5mm mini audio
mono sockets located on the front of the Unit.
• The recommended emitter leads to use with this product are the single head (cat.
no. 8050LD) or the dual head (cat. no. 8050/2LD) IR emitter leads.
• The use of the recommended emitter leads will still allow the supplied remote for
the device to function as the emitter head is transparent to IR.
• Extension leads may be used on the emitter leads of up to 50m of category 5 or
similar cable, such that the cable capacitance does not exceed 10nF.
• The 3.5mm mini audio sockets are NOT isolated from C-Bus. Care must be
taken to ensure that these connector housings are not grounded, or otherwise
connected to an earth referenced voltage source (must be left floating).
© Copyright 2002 Clipsal Integrated Systems Pty Ltd Page 4