1.5 C-Bus Cable Current
The maximum amount of current allowed to flow on Cat-5 UTP cable is 2A. This is a limitation of the
cable. If 2 A is exceeded, you run the risk of damaging the C-Bus cable.
1.6 System Voltage
At all points in a C-Bus network, the voltage across a C-Bus unit must be within the range of 15V to
36Vd.c. However, a C-Bus voltage as low as 15Vd.c., may cause unstable communication. As a rule
of thumb, it is strongly recommended that the C-Bus voltage be maintained at 20Vd.c. or higher.
IMPORTANT Within an individual network, try to evenly distribute C-Bus power supplies
along the network. This will ensure a minimal voltage drop over the
C-Bus cable.
1.7 Units per Network
Two factors determine how many units can be put onto a C-Bus Network. These are:
• network impedance
• current consumption.
To calculate the maximum number of C-Bus units allowed on a network, add the current consumption
of all the inputs, system support units and outputs that do not have power supplies. The combined
current consumption of all these devices must not exceed 2A.