5502DAL C-Bus DALI Gateway Installation Instructions
© 2011 Schneider Electric. All Rights Reserved.
4.0 C-Bus Indicators
4.1 Unit/Comms Indicator
If the unit is powered and functional, the unit/comms indicator will be illuminated
and steady. During data transfer on the RS232 port the unit/comms indicator
will flash.
C-Bus Group Address DALI Address
ON Power on and functional
Flashing Data exchange in progress
4.2 C-Bus Indicator
This indicator shows the status of the C-Bus network at this unit. If sufficient
network voltage and a valid C-Bus clock signal are present then the “OK” signal
will be displayed (steady on). If a network is connected, which has more current
load than the power supplies can support, this indicator will flash to show a
marginal network voltage. If there is no C-Bus network clock present this indicator
will not light.
C-Bus Group Address DALI Address
ON C-Bus network operational
Flashing Insufficient power to support network
OFF No C-Bus clock present or insufficient power
to support network or C-Bus not connected
(check terminations)